T155 Dual Gas
SF6 and g3 Gas-Insulated Substations up to 420 kV
GE's T155 Dual Gas GIS meets the challenges of networks up to 420 kV for power generation, transmission, and heavy industry applications. Ready for future SF6 gas regulations
Anticipating future SF6 regulations, this Dual-Gas equipment is available with either g³ or SF6 gas as an insulating and switching medium. Based on having the same foundational design, Transmission System Operators (TSOs) can buy the SF6 version today and easily switch to GE’s g³ solution at a later time. The T155 Dual Gas GIS is very compact and accessible, with a bay footprint equivalent to the previous SF6 T155 model. Complete bays are fully assembled in the factory (wired, tested, packaged, and shipped), enabling shorter site works. In addition, the T155 Dual-Gas GIS features an advanced SF6 sealing system with a sealing length divided by two compared to the previous version, improving tightness. Full digital monitoring control and protection capabilities enable the T155 Dual Gas to be readily integrated into the smart grid.
|
Transition from SF6 to g³ technology today to reach your carbon neutrality targets faster. Compare the carbon footprint of your substation using g³ products in place of SF6.
Customer Benefits
Characteristics
Sustainability
High availability
Low costs of land and civil works
Short site works
Smart grid features
Specifications
g3 | Combined g3 bay-SF6 CB | SF6 | |
GIS Type | T155g 420 kV | T155 420 kV | T155 420 kV |
Reference electrotechnical standards | IEC | IEC/IEEE | IEC/IEEE |
Rated voltage | 362-420 kV | 362-420 kV | 362-420 kV |
Withstand voltages | |||
Short-duration power-frequency, phase-to-earth/across open switching device | 650/815 kV | 650/815 kV | 650/815 kV |
Switching impulse, phase-to-earth / across isolating distance | 1050/900(+345) kVp | 1050/900(+345) kVp | 1050/900(+345) kVp |
Lightning impulse, phase-to-earth / across open switching device | 1425/1425(+240) kVp | 1425/1425(+240) kVp | 1425/1425(+240) kVp |
Frequency | 50 Hz | 50/60 Hz | 50/60 Hz |
Continuous current | up to 5000 A | up to 5000 A | up to 5000 A |
Short-time withstand current | 63 kA | 63 kA | 63 kA |
Peak withstand current | 170 kAp | 170 kAp | 170 kAp |
Duration of short-circuit | 3s | 3s | 3s |
Installation | indoor/outdoor | indoor/outdoor | indoor/outdoor |
Circuit Breaker Ratings | |||
Short-circuit breaking current | 63 kA | 63 kA | 63 kA |
Short-circuit making current | 170 kAp | 170 kAp | 170 kAp |
Operating sequence | O-0.3s-CO-3 min-CO/CO-15s-CO | O-0.3s-CO-3 min-CO/CO-15s-CO | O-0.3s-CO-3 min-CO/CO-15s-CO |
Drive type | Pure-spring | Pure-spring | Pure-spring |
Mechanical endurance | M2 class | M2 class | M2 class |
Capacitive switching | C2 class | C2 class | C2 class |
Disconnector and Low-speed Earthing Switch Ratings | |||
Capacitive current switching | 0.5 A | 0.5 A | 0.5 A |
Bus-transfer current switching capability | 3000 A / 20 V | 3000 A / 20 V | 3000 A / 20 V |
Mechanical endurance | M2 class | M2 class | M2 class |
Make-proof Earthing Switch Ratings | |||
Making current capability | 170 kAp | 170 kAp | 170 kAp |
Switching capability-electromagnetic coupling | 160 A / 10 kV | ||
Switching capability-electrostatic coupling | 18 A / 20 kV | 18 A / 20 kV | 18 A / 20 kV |
Mechanical endurance | M1 class | M1 class | M1 class |